40
Chapter 6│Parameters
6.1 Group A, Initialization
Sets the initial parameters (group A parameter) such as Access Level Selection, password and
etc.
A1 Initialization
A1- 00 Retain
A1- 01 Access Level Selection
Selects access level (edit/ view)
0 : View Only
Access to only parameter A1-01
1 : User-Defined Parameter Access
Access to only parameter A1-01 and A2-00 to A2-31
2 : All Parameter Access
All parameters can be edited and viewed
Note:
· Once the password is set to A1-05, user cannot edit A1-01, A1-03, A2-01 to A2-32 before entering the correct
password in A1-04.
· Once E1-□□= 60 (Program Lockout) is set, user cannot edit any parameters before closing the assigned
terminal, even when A1-01 = 1 or 2.
· When using Modbus communication to edit parameters, it is not possible to edit parameters via keypad until
an ENTER command is given to the drive from the communication.
·
A1- 02 Control Method Selection