EasyManua.ls Logo

Lowara e-SVE - Test Run Configuration Parameters; Special Parameters

Lowara e-SVE
48 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
en Original instructions
37
P60
Multipump Enable Speed
[P27-P26]
rpmx10
This parameter sets the speed that a pump must reach before
starting the next assist pump, after a system pressure drop below the
difference between P02 and P59.
Default: depending on the type of pump.
P61
Multipump Synchronous
Speed Limit [P27-P26]
rpmx10
This parameter sets the speed limit below which the first assist pump
stops.
Default: depending on the type of pump.
P62
Multipump Synchronous
Window [0-100]
rpmx10
This parameter sets the speed limit for the stop of the next assist
pump.
Default: 150 rpmx10.
P63
Multipump Priority
This parameter shows the pump priority value within the multi-pump
set.
This parameter displays the following information:
Pr1
(Pr1) ..
Pr3
(Pr3) or
Pr0
(Pr0)
where:
Pr1 .. PR3, indicate that the pump is communicating with others
pumps and its priority order, is equal to the visualized number.
Pr0 indicates that the pump does not detect the communication
with other pumps and is considered alone in the multi-pump bus
P64
Multipump Revision
This parameter shows the multi-pump protocol revision value used.
6.5.7 Test Run Configuration Parameters
Test Run is a function that starts the pump after the last stop, in order to prevent it from blocking.
No.
Parameter
Unit of
measurement
Description
P65
Test Run Time Start
[0-100]
h
This parameter sets the time after which, once the pump has
stopped for the last time, the Test Run will start.
Default: 100 h.
P66
Test Run Speed [Min-
Max]
rpmx10
This parameter sets the pump rotational speed for the Test
Run.
The Min and Max speeds depend on the pump type.
Default: 200 rpmx10.
P67
Test Run Time
Duration[0-180]
s
This parameter sets the duration of the Test Run.
Default: 10 s.
6.5.8 Special Parameters
No.
Parameter
Unit of
measurement
Description
P68
Default Values Reload
[
NO, rES
]
If set to RES, after confirmation this parameter performs a
factory reset that reloads the default parameter values.
P69
Avoid Frequent
Parameters Saving [NO,
YES]
This parameter limits the frequency with which the unit stores
the required value P02 in the EEPROM memory, in order to
extend its life.
This could be particularly useful in applications with BMS
control devices that require continuous variation of the value
for fine tuning purposes.
Default: NO.

Table of Contents

Related product manuals