EasyManua.ls Logo

Lowara e-SVE - Example: Ramp Settings; Example: Effective Required Value

Lowara e-SVE
48 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
en Original instructions
39
6.6.2 Example: Ramp Settings
Graph
Figure 18: Ramp settings
Table 13: Description
1
P01 (Required Value)
2
P37 (Adjustment hysteresis) as a % of P36 (Adjustment window)
3
P36 (Adjustment window) as a % of P01 (Required Value)
4
P35 (Minimum speed - Duration)
5
P27 (Minimum speed)
6
Actual Head
7
Actual Speed
RA
P32 (Acceleration ramp at startup)
RB
P32 (Deceleration ramp at shutdown)
R1
P28 (Ramp 1) - Fast ramp speed increase
R2
P29 (Ramp 2) - Fast ramp speed decrease
R3
P30 (Ramp 3) - Slow ramp speed increase
R4
P31 (Ramp 4) - Slow ramp speed decrease
For further information on the adjustment of the ramps, see Par. 6.5.3.
6.6.3 Example: Effective Required Value
Pumps activation in cascade modes:
1. Lead pump reaches its P60 (Enable Speed).
2. Actual value falls to the cut in-value of the 1st assist pump.
The 1st assist pump switches on automatically. (Cut-in value = P01 (Required Value) - P59
(Actual Value Decrease))
3. A new required value, P02 (Effective Required Value) is calculated after the start up.
H [bar]
t [s]

Table of Contents