Chapter 5 High-speed Link Setting
5-8
2) Communication module setting parameter
Communication module parameter setting is as shown below.
Parameter
Setting item
Description
Communication
module Setting
Module
type
Rnet
Base no.
Setting range: 0 ~ 7
It is different from CPU module.
Slot no
Setting range: 0 ~ 11
It is different from type of base.
Communication period
settings
(Period type)
Select among the 20ms, 50ms, 100ms,
200ms, 500ms, 1s, 5s, 10s.
- Default: 200ms
- It is only for transmission data.
- Received data is processed every end of
scan program.
Output data
setting in case
of emergency
CPU
error
Latch
Keep the output status.
(But, P devices data is cleared.)
Clear
Clear all of the output.
CPU
stop
Latch
Keep the output status.
(But, P devices data is cleared.)
Clear
Clear all of the output.
Click OK button after the setting is finished.
Cautions of communication period setting
1) Setting value of communication period is applicable to transmission data (CPU modules data
Rnet I/F module). If communication period is longer than the time of changing data at scan
program, it might be different from the data which is transmitted to slave module.