Chapter4. Inverter Parameter
14
Code
Number
The name of
Parameter
Initial
Value
Range Definition
CM-58
Para Control-8
0x0000
0~0xFFFF
CM-94 Comm Update 0
0:NO
1:YES
Update keypad
parameters relating to
communication.
Table 7 Inverter Parameters
4.2 Description of Profibus-DP Communication Parameters
4.2.1 Version of Communication module
It displays the version of Profibus-DP module installed on the inverter.
4.2.2 Station ID setting
The parameter sets the value of Station ID at Profibus-DP module.
Station ID can be set up within the range of 1~125 and it cannot be
duplicated to write. It needs to check if the settled Station ID is not
equal to other Station ID in network.
If the value of Station ID is changed, set CM-94(Comm Update) to
‘1’ to apply the changed value of Station ID to Profibus-DP
Communication module.
CM-07 FBus ID
CM-94 Comm Update