EasyManua.ls Logo

LSIS LSLV-G100 - Page 123

LSIS LSLV-G100
343 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Auxiliary Reference Operation E.g.
#1
Keypad Frequency Setting is Main Frequency and V1 Analog Voltage is Auxiliary
Frequency
Main frequency: Keypad (operation frequency 30 Hz)
Maximum frequency setting (dr.20): 400 Hz
Auxiliary frequency setting (bA.01): V1[Display by percentage(%) or auxiliary
frequency (Hz) depending on the operation setting condition]
Auxiliary reference gain setting (bA.03): 50%
In.01-32: Factory default output
Example: an input voltage of 6V is supplied to V1, and the frequency corresponding to
10 V is 60 Hz. The table below shows the auxiliary frequency A as 36 Hz[=60 Hz X (6
V/10 V)] or 60%[= 100% X (6 V/10 V)].
Setting*
Calculating final command frequency
0
M[z]+(G[%]*A[Hz])
30 Hz(M)+(50%(G)x36 Hz(A))=48 Hz
1
M[Hz]*(G[%]*A[%])
30 Hz(M)x(50%(G)x60%(A))=9 Hz
2
M[Hz]/(G[%]*A[%])
30 Hz(M)/(50%(G)x60%(A))=100 Hz
3
M[Hz]+{M[Hz]*(G[%]*A[%])}
30 Hz(M)+{30[Hz]x(50%(G)x60%(A))}=39 Hz
4
M[Hz]+G[%]*2*(A[%]-50[%])[Hz]
30 Hz(M)+50%(G)x2x(60%(A)50%)x60
Hz=36 Hz
5
M[HZ]*{G[%]*2*(A[%]-50[%])}
30 Hz(M)x{50%(G)x2x(60%(A)50%)}=3 Hz
6
M[HZ]/{G[%]*2*(A[%]-50[%])}
30 Hz(M)/{50%(G)x2x(60%50%)}=300 Hz
7
M[HZ]+M[HZ]*G[%]*2*(A[%]-
50[%])
30 Hz(M)+30 Hz(M)x50%(G)x2x(60%(A)
50%)
=33 Hz
*M: Main frequency reference/ G: Auxiliary reference gain (%)/ A: Auxiliary
frequency reference (Hz or rpm) or gain (%)
Auxiliary Reference Operation E.g.
#2

Table of Contents

Related product manuals