EasyManuals Logo

LSIS LSLV-G100 User Manual

LSIS LSLV-G100
343 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #143 background imageLoading...
Page #143 background image
5.9 Auto-tuning
The motor parameters can be measured automatically and can be used for auto
torque boost or sensorless vector control.
Example - Auto-Tuning Based on 0.75kW, 200V, 60Hz, 4 Pole Motor
Group
Code
Name
Setting
Setting Range
Unit
dr
14
Motor capacity
1
0.75 kW
015
-
bA
11
Number of motor
poles
4
248
-
12
Rated slip speed
70
03000
Rpm
13
Motor rated
current
3.3
1.01000.0
A
14
Motor noload
current
1.7
0.51000.0
A
15
Motor rated
voltage
220
170480
V
16
Motor efficiency
83
64100
%
20
Auto tuning
0
None
-
-
21
Stator resistance
2.951
Depends on the motor
setting
Ω
22
Leakage
inductance
25.20
Depends on the motor
setting
mH
23
Stator
inductance
171.1
Depends on the motor
setting
mH
24
Rotor time
constant
137
255000
ms

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the LSIS LSLV-G100 and is the answer not in the manual?

LSIS LSLV-G100 Specifications

General IconGeneral
BrandLSIS
ModelLSLV-G100
CategoryInverter Drive
LanguageEnglish

Related product manuals