Code and
Features
Description
Pr.41 Motor
Cooling
Select the drive mode of the cooling fan, attached to the motor.
Configuration
Function
0
Self-cool
As the cooling fan is connected to the motor
axis, the cooling effect varies, based on motor
speed. Most universal induction motors have
this design.
1
Forced-
cool
Additional power is supplied to operate the
cooling fan. This provides extended operation
at low speeds. Motors designed for inverters
typically have this design.
Pr.42 ETH 1min
The amount of input current that can be continuously supplied to the
motor for 1 minute, based on the motor-rated current (bA.13).
Pr.43 ETH Cont
Sets the amount of current with the ETH function activated. The
range below details the set values that can be used during
continuous operation without the protection function.