7.3.1.1 Detailed Read Protocol
Read Request: Reads successive n words from address XXXX.
ENQ
Station ID
CMD
Address
Number of
Addresses
SUM
EOT
05h
‘01’–’FA’
‘R’
‘XXXX
‘1’–‘8’ = n
‘XX’
04h
1 byte
2 bytes
1 byte
4 bytes
1 byte
2 bytes
1 byte
Total bytes=12. Characters are displayed inside single quotation marks (‘).
Read Normal Response
ACK
Station ID
CMD
Data
SUM
EOT
06h
‘01’–‘FA’
‘R’
‘XXXX
‘XX’
04h
1 byte
2 bytes
1 byte
n x 4 bytes
2 bytes
1 byte
Total bytes= (7 x n x 4): a maximum of 39
Read Error Response
NAK
Station ID
CMD
Error Code
SUM
EOT
15h
‘01’–‘FA’
‘R’
‘**’
‘XX’
04h
1 byte
2 bytes
1 byte
2 bytes
2 bytes
1 byte
Total bytes=9