11 Technical Specification
11.1 Input and Output Specification
3 Phase 200 V (0.47.5 kW)
Model Name
LSLVG100-2□□□□
0004
0008
0015
0022
0040
0055
0075
Applied
motor
Heavy
load
HP
0.5
1.0
2.0
3.0
5.0
7.5
10
kW
0.4
0.75
1.5
2.2
4.0
5.5
7.5
Normal
load
HP
1.0
2.0
3.0
5.0
7.5
10
15
kW
0.75
1.5
2.2
4.0
5.5
7.5
11
Rated
output
Rated
capacity
(kVA)
Heavy
load
1.0
1.9
3.0
4.2
6.5
9.1
12.2
Normal
load
1.2
2.3
3.8
4.6
6.9
11.4
15.2
Rated
current (A)
[3-Phase
input]
Heavy
load
2.5
5.0
8.0
11.0
17.0
24.0
32.0
Normal
load
3.1
6.0
9.6
12.0
18.0
30.0
40.0
Rated
current (A)
[1-Phase
input]
Heavy
load
1.5
2.8
4.6
6.1
9.3
12.8
17.4
Normal
load
2.0
3.6
5.9
6.7
9.8
16.3
22.0
Output frequency
0400 Hz(IM Sensorless: 0120 Hz)
Output voltage (V)
3-phase 200240 V
Rated
input
Working voltage (V)
3-phase 200240 VAC (-15% to +10%)
Single phase 240VAC(-5% to +10%)
Input frequency
5060 Hz (5%)
(In case of single phase input, input frequency is only
60Hz(
5%).)
Rated
current (A)
Heavy
load
2.2
4.9
8.4
11.8
18.5
25.8
34.9
Normal
load
3.0
6.3
10.8
13.1
19.4
32.7
44.2
Weight (lb /kg)
1.04
1.06
1.36
1.4
1.89
3.08
3.21
The standard motor capacity is based on a standard 4-pole motor.
The standard used for 200 V inverters is based on a 220 V supply voltage, and for 400 V
inverters is based on a 440 V supply voltage.
The rated output current is limited based on the carrier frequency set at Cn.04.
The output voltage becomes 2040% lower during no-load operations to protect the inverter