11.5 Fuse and Reactor Specifications
Capacity (kW)
AC Input Fuse
AC Reactor
Model
Current (A)
Voltage
(V)
Inductance (mH)
Current (A)
3-phase
200 V
0.4
DFJ-10
1)
10
600
1.20
10
0.75
1.5
DFJ-15
15
0.88
14
2.2
DFJ-20
20
0.56
20
4.0
DFJ-30
30
0.39
30
5.5
DFJ-50
50
0.30
34
7.5
DFJ-60
60
0.22
45
3-phase
400 V
0.4
DFJ-10
10
4.81
4.8
0.75
1.5
3.23
7.5
2.2
DFJ-15
15
2.34
10
4.0
DFJ-20
20
1.22
15
5.5
DFJ-30
30
1.12
19
7.5
DFJ-35
35
0.78
27
Note
1
) DFJ is Class J/600 V level model name of the Bussmann company.
Use Class CC, G, J, L, R or T UL Listed Input Fuse and UL Listed Breaker Only. See the
table above For the Voltage and Current rating of the fuse and the breaker.
Utiliser UNIQUEMENT des fusibles d’entrée homologués de Classe CC, G, J, L, R ou T
UL et des disjoncteurs UL. Se reporter au tableau ci-dessus pour la tension et le courant
nominal des fusibless et des disjoncteurs.