To connect cables to the control terminals without using crimp terminals, refer to the
following illustration detailing the correct length of exposed conductor at the end of the
control cable.
Note
While making wiring connections at the control terminals, ensure that the total cable
length does not exceed 165 ft (50 m).
Ensure that the length of any safety related wiring does not exceed 100 ft (30m).
Use ferrite material to protect signal cables from electro-magnetic interference.
Take care when supporting cables using cable ties, to apply the cable ties no closer
than 6 inches from the inverter. This provides sufficient access to fully close the front
cover.
When making control terminal cable connections, use a small flat-tip screw driver (0.1
in wide (2.5 mm) and 0.015 in thick (0.4 mm) at the tip).