3.4.2 Trip Condition Monitor
The following example demonstrates how to monitor fault trip conditions in the
Operation group using the keypad.
Step
Instruction
Keypad Display
1
Refer to the example keypad display.
An over current trip fault has occurred.
2
Press the [ENT] key, and then the [▲] key.
The operation frequency at the time of the fault (30.00 Hz)
is displayed.
3
Press the [▲] key.
The output current at the time of the fault (5.0 A) is
displayed.
4
Press the [▲] key.
The operation status at the time of the fault is displayed.
ACC on the display indicates that the fault occurred
during acceleration.
5
Press the [STOP/RESET] key.
The inverter resets and the fault condition is cleared. The
frequency reference is displayed on the keypad.