Choose the P1-P5 terminals to setup as multi-step inputs, and then set
the relevant codes (In.65–69) to 7 (Speed-L), 8 (Speed-M), or 9
(Speed-H).
Provided that terminals P3, P4 and P5 have been set to Speed-L,
Speed-M and Speed-H respectively, the following multi-step operation
will be available.
[An example of a multi-step operation]
After adjusting In.89 to 100 ms and an input signal is received at P5,
the inverter will search for inputs at other terminals for 100 ms, before
proceeding to accelerate or decelerate based on P5’s configuration.