2. Troubleshooting
24
Occurs when the temperature of the heat sink exceeds the
specific value.
There is a problem with the cooling
system.
Check whether there are any external substances (dust, etc.) in the
air inlet, outlet or vent.
The cooling fan has been operating
for a long time
Change the cooling fan. (Refer to 3.1.5 Replace cooling fan)
The ambient temperature is too high.
Keep the ambient temperature below 50ā.
Occurs when there is a problem with the cooling fan.
Operation will resume after setting Pr.79 1 to 0 (<22kW).
There are external substances
blocking the air vent.
Remove the external substances.
The cooling fan needs to be
replaced.
Change the cooling fan. (Refer to 3.1.5 Replace cooling fan)
Occurs when the I/O Board or the communication card is
not (or poorly) connected to the inverter.
There is a communication problem
with the loader that is connected to
the inverter and the remote loader.
Check whether the communications line is properly connected.