1) Set H49 to 1 (PID control) to display this parameter.
2) Set H49 as a 1
3): it is indicated when setting H64(KEB drive select) as a 1 (KEB does not operate when cut power after loading ting input (about 10%).
LED
display
Address for
communication
Parameter
name
Min/Max
range
Description
Adj.
during run
Factory
defaults
Function group 2
0 Terminal I input (0 ~ 20 mA)
1 Terminal V1 input (0 ~ 10 V)
This parameter sets the gains for the PID controller.
Selects PID control mode
0 Normal PID control
1 Process PID control
This parameter limits the amount of the output frequency through
the PID control.
The value is settable within the range of F21 ? [Max frequency]
and F23 - [Start frequency].
Selects PID standard value.
Standard value is indicated in “rEF” of Drive group.
0 Loader digital setting 1
1 Loader digital setting 2
2 V1 terminal setting 2: 0~10V
3 I terminal setting: 0~20mA
4 Setting as a RS-485 communication
Selects a unit of the standard value or feedback amount.
0 Frequency[Hz]
1 Percentage[%]
0 Self-diagnostic disabled
1 IGBT fault/Ground fault
2 Output phase short & open/ Ground fault
3 Ground fault (This setting is unable when more than 11kW)
Sets a sleep delay time in PID drive.
Sets a sleep frequency when executing a sleep function in PID
control drive.
You canʼt set more than Max. frequency(F21)
Sets a wake up level in PID control drive.
Sets KEB drive.
Sets KEB action start level according to level.
Sets KEB action stop level according to level.
Sets KEB action gain.
0 Based on Max freq (F21)
1 Based on Delta freq.
0 X
300.0 O
1.0 O
0.0 O
0 X
60.00 O
0.50 O
0 X
0 X
0 X
60.0 X
0.00 O
35.0 O
0 X
125.0 X
130.0 X
1000 X
0 X
H50
H51
H52
H53
H54
H55
H56
H57
H58
H60
H61
H62
H63
H64
H65
H66
H67
H70
A332 [PID F/B select] 0 ~ 1
A333 [P gain for PID]
0~ 999.9
[%]
A334
[Integral time 0.1~32.0
for PID [sec]
A335
[Differential time 0 ~ 30.0
for PID (D gain)] [sec]
A336
[PID control
0~1
mode select]
[PID output
0.1 ~ 400
A337 frequency high
[Hz]
limit]
[PID output
0.1 ~ 400
A338 frequency low
[Hz]
limit]
A339
[PID standard
0~4
value select]
A33A
PID control
0~1
unit select
A33C
[Self-diagnostic
0 ~ 3
select]
A33D [Sleep delay time] 0~2000[s]
A33E [Sleep frequency] 0~400[Hz]
A33F [Wake up level] 0~100[%]
A340 [KEB drive select] 0~1
A341
[KEB action 110~140
start level] [%]
A342
[KEB action 110~145
stop level] [%]
A343
[KEB action
1~20000
gain]
[Frequency
A346 Reference for 0 ~ 1
Accel/Decel]
1)
2)
33
Compact & Powerful Drive iG5A
Drive Starvert iG5A Series