Lucent Technologies Enhanced VR Series Batteries
Issue 5 December 1998 Battery Storage 5 - 1
5 Battery Storage
State of New
Battery
The Enhanced VR battery is shipped in the charged state. The
open circuit voltage for a fully charged battery is approximately
2.15V/cell.
Storage
Conditions
Store batteries in an upright position in a dry and cool
environment without exposure to direct sunlight.
Provide adequate ventilation during storage.
Do not stack pallets of batteries on top of each other during
storage.
Storage Time
Batteries may suffer irreversible capacity loss during long open
circuit stand. The maximum that a charged battery may remain
on open circuit is 6 months at 77°F. The open circuit time should
not exceed 4 months if the storage temperature exceeds 90°F.
The “charge by” date stamped on the shipping container is the
date the battery has been on open circuit for 6 months. If
batteries cannot be installed within this time period, follow the
procedures outlined in Table 6-A, “Initial Charging,” and record
the actions taken until normal installation can be initiated.

Table of Contents