Lucent Technologies Enhanced VR Series Batteries
6 - 8  Installation   Issue 5  December 1998
Placing a 
Battery String 
Into Service
Batteries should be in service within 48 hours of initial charge. 
If a battery is left on open circuit for more than 48 hours after the 
initial charge, treat it as if it had never received an initial charge.
Since battery performance is based on the output at the battery 
terminals, the shortest electrical connection between the battery 
system and the operating equipment results in the maximum 
total system performance.
Cable size should be specified and installed that will maintain 
appropriate voltage drop between the battery system and the 
operating equipment. Excess voltage drop will reduce the 
desired reserve time of the battery system.
When paralleling valve-regulated batteries, the capacity, 
arrangement, and external circuit length should be identical for 
each battery. Wide variations in the battery circuit resistance can 
result in unbalanced charging (i.e., excess charging current in 
some batteries and undercharging in others). As a result, cell 
failures in one battery string and subsequent loss of performance 
capabilities of that string will result in higher loads in the other 
parallel string(s), which may exceed the ratings of the battery 
connections. This can damage the battery and dramatically 
shorten battery life.
Installation 
Records
The “Installation and Maintenance Record” (see Section 10) is 
required for warranty validation. The installer should use this 
form to record the following measurements. 
Voltage
Measurements
Before connecting parallel strings together or individual strings 
to the plant bus, make the following voltage measurements: 
1. Measure individual battery voltage. Replace any 2VR250 
or 2VR375 battery with a voltage less than 2.0 volts or any 
4VR125 battery with a voltage less than 4.0 volts.
2. Measure across the string to verify that the batteries are 
connected properly and that the polarity is correct. The 
string voltage should be equal to the sum of the individual 
battery readings recorded above. 
3. Measure across the plant charge and discharge battery 
buses. The voltage difference between the string and plant 
should not exceed 0.05 volts unless the plant is at 0 (zero)