Lucent Technologies Enhanced VR Series Batteries
9 - 2 Discharge and Power Data Issue 5 December 1998
Table 9-A: 2VR375E Constant Current Discharge Data
Hours
Reserve @
77° F
End Volts per Battery
1.75 1.80 1.82 1.84 1.86 1.88 1.90 1.92
1 161.8 150.6 144.7 137.9 131.4 129.1 119.6 109.0
3 84.1 82.8 81.7 80.2 78.4 76.2 73.3 70.0
5 61.7 61.0 60.3 59.3 58.1 56.4 54.0 51.0
8 44.5 43.7 43.3 42.8 41.9 40.8 39.2 37.4
10 37.8 37.3 36.9 36.5 35.9 35.0 33.8 32.4
15 28.5 28.1 28.0 27.6 27.2 26.6 25.7 24.9
20 22.5 22.3 22.1 21.9 21.5 21.1 20.4 19.6
24 19.4 19.2 19.1 18.9 18.5 18.2 17.6 16.9
Table 9-B: 4VR125EL Constant Current Discharge Data
Hours
Reserve @
77° F
End Volts per Battery
1.75 1.80 1.82 1.84 1.86 1.88 1.90 1.92
1 55.1 52.1 50.3 48.2 45.9 43.6 42.2 38.8
3 28.1 27.7 27.5 27.0 26.5 25.8 24.9 23.6
5 20.6 20.4 20.2 19.9 19.5 19.0 18.3 17.2
8 14.8 14.6 14.5 14.3 14.1 13.7 13.2 12.6
10 12.6 12.4 12.3 12.2 12.0 11.7 11.4 10.9
15 9.4 9.3 9.2 9.1 9.0 8.9 8.6 8.3
20 7.5 7.4 7.4 7.3 7.2 7.0 6.8 6.6
24 6.5 6.4 6.4 6.3 6.2 6.1 5.9 5.7