EasyManuals Logo

Lucent Technologies VR Series User Manual

Lucent Technologies VR Series
82 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #67 background imageLoading...
Page #67 background image
Lucent Technologies Enhanced VR Series Batteries
Issue 5 December 1998 Discharge and Power Data 9 - 13
High
Discharge Rate
Performance
The Enhanced VR battery is also appropriate for applications
requiring high discharge rate performance. Table
9-G lists 1-minute and 5-minute rates to 1.75 volts per battery at
77° F. These data have been adjusted for intercell and/or interior
connector losses, but not for connections between the battery
and the load.
Table 9-G: High Discharge Rate Performance
Module
End
Voltage/Battery
Reserve @ 77° F
1 minute 5 minutes
2VR375E 1.75 Volts 570 amperes 495 amperes
2VR250E 1.75 Volts 370 amperes 320 amperes
4VR125EL 1.75 Volts 185 amperes 160 amperes