Lucent Technologies Enhanced VR Series Batteries
7 - 6 Operation Issue 5 December 1998
67°F (19.4° C). Therefore, the temperature-corrected capacity is
97.5% + 2.5% = 100% (full capacity).
Note
When the ambient temperature is above 25°C (77°F),
subtract the correction factor and vice versa.
Corrected capacity = Measured Capacity * [1 - 0.0025
(Temp°F - 77°F)]
Figure 7-1: Temperature Correction Chart
10
9
8
-8
30 40 50 60
Cell Temperature (°F) at Start of Discharge
70 80 90 100
7
Temperature Correction for
Capacity to 1.75 Volts
-7
6
-6
5
-5
4
-4
3
-3
2
-2
1
Percentage Capacity Correction , K
-1
0