Lucent Technologies Enhanced VR Series Batteries
7 - 8  Operation   Issue 5  December 1998
Recharge After 
Discharge
Recharge should be carried out at the normal float voltage of 
2.25 volts per 2VR250E or 2VR375E module or 4.5 volts per 
4VR125E or 4VR125EL module or temperature-compensated 
voltage. The recharge should begin as soon as possible after the 
discharge.
Boost Charge
Boost charging the Enhanced VR Series batteries is not 
recommended without the concurrence of Lucent 
Technologies. Call 1-800-225-7822 for technical assistance.
During a boost charge, water loss due to electrolysis is greatly 
increased. In valve regulated, lead acid cells, frequent or 
prolonged boost charges can result in premature failure caused 
by cell dry-out. Boost charging at elevated battery temperatures 
can be especially detrimental to the batteries.