3.6 Ground/Base
Dehumidifier must be installed horizontally with well-balanced level. Please use horizontal ruler to
measure the level during installation.
3.7 Ducting Connection
The dimension of ducting for inlet and outlet air should be in line with ISO7807 recommended
values. Ducting should be connected with the connection part on flange, meanwhile, the screw bolt
is limited to within 20mm. While connecting the ducting, some notes as below:
In order to reduce loss of static pressure, do the best to shorten the length of the ducting;
To ensure performance of machine, all rigid (galvanized) ducting fittings are required to have
air-tightness;
The ducting should have a good capacity of thermal insulation, then the phenomenon of
moisture condensation inside pipe wall will be avoided, and the pipeline won't be corroded;
To reduce noise and vibration transmitted along the pipes, the good quality, soft and strong
airtight adapting pieces should be used in the joint parts;