LUKO FD-S60L - 4.9 Error Code Address Details; 4.10 Safety Cautions

Default Icon
35 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Page
26
of
35
0x101C
03/16/16
working modes
2 bytes
Read/Write
0 - dehumidification
1 cooling + dehumidification
2 heating + dehumidification
3 cooling + humidification
4 heating + humidification
5 - humidification
0x101D
03/16/16
humidification set
2 bytes
Read/Write
1~99
0x2001
03
indoor temperature sensor
2 bytes
Read Only
0x2002
03
indoor humidity sensor
2 bytes
Read Only
0x2003
03
external temperature sensor
2 bytes
Read Only
0x2004
03
external humidity sensor
2 bytes
Read Only
0x2005
03
fan running time
2 bytes
Read Only
1=10 hours
0x2006
03
failure
2 bytes
Read Only
bit0: built sensor failure
bit1: external sensor failure
bit2: filter alarm
bit3: minimum absolute humidity
protection
bit4: in defrost
0x2007
03
dew point
2 bytes
Read Only
0x2008
03
absolute humidity
2 bytes
Read Only
4.10Safety Cautions
Dehumidifier has high-speed moving parts. Before running, make sure panel is closed correctly and
no debris present at the exterior. Do not use force to open the machine during operation otherwise,
it will cause serious consequences to dehumidifier.
A. Temperature and humidity sensors are sensitive components, do not touch the components;
B. All wires are distinguished by colors, please let professionals do the wiring work;
C. Temperature and humidity control should be placed in clean environment. Acetone, chlorine
or high concentrations smoke and will cause damage;
D. Humidistat is sensitive to ambient humidity. Do not place in dusty area.
E. If some problem happened to the dehumidifier, it would stop. Please check the machine first
before turning on again.
F. Don’t move dehumidifier or unplug until the fan stops;