4.5 Mode / Function
4.5.1 Dehumidification Working Mode:
Working mode
H04=0
Function
Dehumidification
Relay 1
High fan speed
Relay 2
Medium fan speed
Relay 3
Low fan speed
Relay 4
Compressor
Relay 5
Air damper open
4.5.2 Description
If the humidity of the air is higher than the setting, the fan turns on; 5 seconds later,
the compressor turns on.
If the humidity of the air is lower than the setting, the compressor turns off; 3 minutes later,
the fan turns off.
4.5.3 Initial Value
Initial Value
The controller has data memory function when there is power failure.
The initial value as below:
*Fan speed: High
*Air damper: close
*Mode: the same before the power failure
4.5.4 Fan Control
I. The initial value is high speed, can be adjusted manually.
II. DC motor (0~10V) fan has 5 fan speeds, which can be set separately.
III. AC motor fan speed can be adjusted manually when H04=0:
a. F01 = 1, High fan speed available
b. F01 = 2, High fan speed & low fan speed available
c. F01 = 3, High fan speed & medium fan speed & low fan speed available
IV. High fan speed & low fan speed available when H04=1.
V. High fan speed available when H04=2.
Fan works according to F02 when achieve the set humidity and temperature (only for the available
system working mode):
F02 = 1, The fan turns off 3 minutes later after achieved the set humidity and temperature
(only for the available system working mode)