LUKO FD-S60L - 4.5.4 Fan Control Details; 4.5.5 Air Damper Control; 4.5.6 Defrost Control; 4.5.7 Alarm

Default Icon
35 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Page
23
of
35
F02 = 2, The fan keeps working after achieved the set humidity and temperature
(only for the available system working mode)
4.5.5 Air Damper Control
Air damper works according to H01, R03 when the unit is turned on manually.
I. Open or close air damper manually when H01=0:
a. Air damper close: 100% return air
b. Air damper open: mixed fresh and return air
II. Open or close air damper automatically when H01=1:
a. Indoor humidity R03: air damper close; Indoor humidity R03~R04: air damper
open.
b. Can switch to manual mode from automatic mode and works manually for 30 minutes
and continue to work automatically.
c. Air damper close when the unit is powered off manually.
4.5.6 Defrost Control
4.9.1 Defrost conditions: Indoor temperature D3
4.9.2 Defrost mode: compressor cycle off & fan runs at high speed
4.9.3 Defrost stop conditions:
a. Defrost time D2.
b. Unit is turned off manually.
c. Unit is turned off faulty.
4.5.7 Alarm
a. Filter Alarm
b. Built-in temp. & humidity sensor error
c.RS485-1 Communication Error