RS485-2 Address
P02
1
1~255
RS485-2 Protocol
P03
0
General open protocol
RS485-2 Communication status
007
0 - abnormal
1 - normal
Software version
009
Dew point
010
Absolute humidity
011
4.7 Working Status Display
Type
Range
Precision
Indoor temperature
-30~99°C, -22~210°F
0.1°C,1°F
Indoor humidity
0~100%
0.10%
Absolute humidity
0.0~99.9
0.1g/kg
Fan's running time
0~999
10 ours
4.8 Error Code
Error
Code
Built-in temp. & humidity sensor failure
E01
External temp. & humidity sensor failure
E02
RS485-1 communication failure
E03
4.9 Error Code Address
Address
Function
Code
Object
Byte
Read Only or
Read/Write
Data
0x1001
03/16/16
ON/OFF
2 bytes
Read/Write
0 - OFF
1 - ON
0x1002
03/16/16
fan speed
2 bytes
Read/Write
1 - 1st fan speed
2 - 2nd fan speed
3 - 3rd fan speed
4 - 4th fan speed
5 - 5th fan speed
0x1003
03/16/16
air damper close/open
2 bytes
Read/Write
0 - close
1 - open
0x1004
03/16/16
humidity set
2 bytes
Read/Write
1~99%
0x1006
03/16/16
air damper automatic humidity set
2 bytes
Read/Write
1~99%
0x1008
03/16/16
air damper automatic close/open
2 bytes
Read/Write
0 - not in use
1 - in use
0x101B
03/16/16
temperature set
2 bytes
Read/Write
5~35°C