IMPULSE
®
•G+ Mini Technical Manual
November 2020
Page 90
5.5 Option Parameters
• F1 Pulse Generated (PG) Control
• F6 Profibus-DP Communication Option Card Setup
• F7 Ethernet Option Card Setup (Ethernet IP & Modbus TCP/IP)
5.5.1 Pulse Generated (PG) Control
The following parameters are used to set and control the action for the Pulse Generated (PG) input and output,
including overspeed detection. These parameters become visible when the pulse generator function (H06.01) is
set to 03 and the control method is set to OLV (A01.02 = 02).
Parameter Name Function Range Default
F01.02 Pulse Feedback Loss Stopping Method for PG Disconnect 00–03 01
00 Decel to Stop (by B05.02)
01 Coast to Stop
02 Fast Stop (by B05.08)
03 Alarm Only
F01.03 Operation at Overspeed Stopping Method for PG Overspeed 00–03 01
00 Decel to Stop (by B05.02)
01 Coast to Stop
02 Fast Stop (by B05.08)
03 Alarm Only
F01.04 Operation at Deviation Stopping Method for PG Deviation 00–07 05
00 @ speed agree - Decel (by B05.02)
01 @ speed agree - Coast to Stop
02 @ speed agree - Fast Stop (by B05.08)
03 @ speed agree - Alarm only
04 @ Run - Decel to Stop (by B05.02)
05 @ Run - Coast to Stop
06 @ Run - Fast Stop (by B05.08)
07 Alarm only (Dev-1 and Dev-2 Alarm)
F01.08 Overspeed Detection Level PG Overspeed Detection Level 0−120% 105
F01.09 Overspeed Detection Time PG Overspeed Detection Time 0.0–2.0sec 0.0
F01.10 Excessive Speed Detection Level Excessive Speed Deviation Level 0–50% 10
F01.11 Excessive Speed Detection Time Excessive Speed Deviation Detection
Time
0.0–10.0sec 0.3
F01.14 PGO Detection Time PGO Detection Time 0.0–10.0sec 0.5