5.5.2 Profibus-DP Communication Option Card Setup
Settings for the Profibus-DP communication option card SI-P3.
Parameter Name Function Range Default
F06.01
Comm Bus Fault (BUS) Stopping method when a BUS fault occurs 00-04 01
00 Decel to Stop
01 Coast to Stop
02 Fast-Stop
03 Use B03.03 Method
04 Alarm Only
05 Decel to Stop (Auto Reset)
06 Coast to Stop (Auto Reset)
07 Fast-Stop (Auto Reset)
08 Use B03.03 Method (Auto Reset)
F06.02 Comm External Fault (EF0) External Fault (EF0) detection method via
Profibus-DP
00-01 00
00 Always Detected
01 Only During Run
F06.03 EF0 Fault Action Stopping method when an EF0 fault occurs 00-04 01
00 Decel to Stop
01 Coast to Stop
02 Fast-Stop
03 Use B03.03 Method
04 Alarm Only
F06.08 Comm Parameter
Initalization
Determines whether communication-related
parameters (F06.xx and F07.xx) are reset
when the VFD is initialized with A01.05.
00-01 00
00 Initalize Comm Parameters
01 Don't Initialize Comm Parameters
F06.14 BUS Fault Auto Reset Determines whether a BUS fault will be
automatically reset.
00-01 00
00 Disabled
01 Enabled
F06.30 Profibus Node Address Sets the node address for Profibus-DP
communications.
0-125 00
F06.31 Profibus Clear Select Determines the operation when a “Clear
Mode” command is received on the Profibus-
DP option card.
00-01 00
00 Reset to Zero
01 Hold Previous Value