EXCITATIONENABLE/DISABLE-thismessagecanbeusedtodisable/enableexcitation.
Message ID: (0xFFA2) Excitation Enable/Disable
Source: ECU1 or ECU2 or ECU3
Message Group: None
PDU Format: 255 (PDU2)
PDU Specific: 162
BYTE 0 BYTE 1 BYTE 2 BYTE 3 BYTE 4 BYTE 5 BYTE 6 BYTE 7
Excit
Enable
Disable
Unused Unused Unused Unused Unused Unused Unused
0xFF 0xFF 0xFF 0xFF 0xFF 0xFF 0xFF 0xFF
Byte 0 ExcitationEnable/Disable-changesthestateofexcitationontheregulator:
0x00 – disables excitation, changing regulator to the OFF state
0x01 – enables excitation, changing regulator to the Run state
Any other value – no change
Byte 1-7 Unused