CD 30 ÷ 520
23
Heating capacity
15
20
25
30
35
40
13ºC 10ºC 7ºC 2ºC -2ºC -6ºC -10ºC
Ambient temperature
Kw
39ºC
42ºC
45ºC
48ºC
50ºC
Heating capacity
7
8
9
10
11
12
13ºC 10ºC 7ºC 2ºC -2ºC -6ºC -10ºC
Ambient temperature
Kw
39ºC
42ºC
45ºC
48ºC
50ºC
8.2. Cooling and heating capacity mod. 65 Kw
Cooling capacity Power input
Outlet water temperature Outlet water temperature
Ambient temp. °C
5ć 7ć 9ć 12ć 5ć 7ć 9ć 12ć
25 67.6 71.5 74.75 75.4 18.49 18.92 19.35 19.995
28 66.95 70.2 73.45 76.70 18.92 19.135 19.565 20.21
30 64.675 68.25 71.5 75.075 19.78 19.8875 20.3 21.0
32 64.4 67.6 70.9 74.1 20.21 20.4 20.9 21.5
35 61.8 65 68.9 71.5 20.9 21.5 22.1 22.6
38 59.8 63.1 66.3 68.9 22.1 22.6 23.2 23.2
40 58.5 61.1 64.4 67.6 22.8 23.2 23.9 23.9
The diagram shows the capacity
progress among ambient
temperature and outlet water
temperature of 39°C, 42°C,
45°C, 48°C, 50°C
The diagram shows the power
input progress among ambient
temperature and outlet water
temperature of 39°C, 42°C,
45°C, 48°C, 50°C