86 IOMM ACZ/AGZ-1
Table 47, MENU 20 Schedule
Screen Display Factory Setpoint Range
1 Override= xx.xx hr 0.00 Hr 00:00 - 63.50
2 NMPSchedule= N/A N/A
3 Sun 00:00-23:59 00:00 - 23:59 00:00 - 23:59
4 Mon 00:00-23:59 00:00 - 23:59 00:00 - 23:59
5 Tue 00:00-23:59 00:00 - 23:59 00:00 - 23:59
6 Wed 00:00-23:59 00:00 - 23:59 00:00 - 23:59
7 Thu 00:00-23:59 00:00 - 23:59 00:00 - 23:59
8 Fri 00:00-23:59 00:00 - 23:59 00:00 - 23:59
9 Sat 00:00-23:59 00:00 - 23:59 00:00 - 23:59
10 Hol 00:00-23:59 00:00 - 23:59 00:00 - 23:59
Table 48, MENU 21 Holiday Date
Screen Display Factory Setpoint Range
1 #1 Date = N/A 0 N/A 0 Jan - Dec 1 - 31
2 #1 Dur = 0 Day(s) 0 0 - 31
3 #2 Date = N/A 0 N/A 0 Jan - Dec 1 - 31
4 #2 Dur = 0 Day(s) 0 0 - 31
5 #3 Date = N/A 0 N/A 0 Jan - Dec 1 - 31
6 #3 Dur = 0 Day(s) 0 0 - 31
7 #4 Date = N/A 0 N/A 0 Jan - Dec 1 - 31
8 #4 Dur = 0 Day(s) 0 0 - 31
9 #5 Date = N/A 0 N/A 0 Jan - Dec 1 - 31
10 #5 Dur = 0 Day(s) 0 0 - 31
11 #6 Date = N/A 0 N/A 0 Jan - Dec 1 - 31
12 #6 Dur = 0 Day(s) 0 0 - 31
13 #7 Date = N/A 0 N/A 0 Jan - Dec 1 - 31
14 #7 Dur = 0 Day(s) 0 0 - 31
15 #8 Date = N/A 0 N/A 0 Jan - Dec 1 - 31
16 #8 Dur = 0 Day(s) 0 0 - 31
17 #9 Date = N/A 0 N/A 0 Jan - Dec 1 - 31
18 #9 Dur = 0 Day(s) 0 0 - 31
19 #10 Date = N/A 0 N/A 0 Jan - Dec 1 - 31
20 #10 Dur = 0 Day(s) 0 0 - 31
21 #11 Date = N/A 0 N/A 0 Jan - Dec 1 - 31
22 #11 Dur = 0 Day(s) 0 0 - 31
23 #12 Date = N/A 0 N/A 0 Jan - Dec 1 - 31
24 #12 Dur = 0 Day(s) 0 0 - 31
25 #13 Date = N/A 0 N/A 0 Jan - Dec 1 - 31
26 #13 Dur = 0 Day(s) 0 0 - 31
27 #14 Date = N/A 0 N/A 0 Jan - Dec 1 - 31
28 #14 Dur = 0 Day(s) 0 0 - 31
Table 49, MENU 22 Alarm Spts
Values for R-22 refrigerant, ( ) indicates Centigrade values
Screen Display Factory Setpoint Range
1 FreezStat= xxpsi (kPa) 54 (372) 20 - 60 (138 - 414)
2 FreezH2O= xx.x °F (°C) 36.0 (2.3) 0.0 - 40.0 (-17.5 - 4.5)
3 FreezeTim= xxx sec
4 Hi Press = xxxpsi (kPa) 380 (2622) 280 - 426 (1932 - 2939)
Table 50, MENU 22 Alarm Spts
Values for 134a refrigerant, ( ) indicates Centigrade values
Screen Display Factory Setpoint Range
1 FreezStat= xxpsi (kPa) 26 (179) 4 - 26 (27 - 179)
2 FreezH2O= xx.x °F (°C) 36.0 (2.3) 0.0 - 40.0 (-17.5 - 4.5)
3 FreezeTim= xxx sec
4 Hi Press = xxxpsi (kPa) 380 (2622) 280 - 426 (1932 - 2939)