MDM Series Units Air Flow Table (I)
HEIGHT COIL HEIGHT WIDTH MODULUS 4M 5M 6M 7M 8M 9M 10M 11M 12M 13M 14M 15M
MODULUS (mm) COIL WIDTH (mm) 420 580 740 900 1060 1220 1380 1540 1700 1860 2020 2180
3M 304.8 1152 1591 2030 2469 2908 3347
4M 457.2 2387 3045 3703 4362 5020 5678 6337
5M 609.6 4060 4938 5816 6693 7571 8449
6M 762 5075 6172 7269 8367 9464 10561 11659
7M 914.4 7407 8723 10040 11357 12674 13990 15307 16624 17941
8M 1066.8 10177 11713 13250 14786 16322 17858 19394 20931
9M 1219.2 13387 15142 16898 18654 20409 22165 23921
10M 658.2 x 2 17035 19010 20985 22961 24936 26911
11M 762 x 2 21123 23317 25512 27706 29901
12M 838.2 x 2 25649 28063 30477 32891
13M 914.4 x 2 30614 33248 35881
14M 990.6 x 2 36018 38871
15M 1066.8 x 2 41861
16M 1143 x 2
17M 1219.2 x 2
18M 1295.4 x 2
Notes:
1) The air flow is on the condition that the face velocity is 2.5m/s
2) 1M = 160mm
3) The standard panel thickness is 33mm
4) Casing Width = Width Modulus × 160+50 (mm)
5) Horizontal Arranged Casing Height = Height Modulus × 160+50 (mm)
6) Vertical Arranged Casing Height = 2 × (Height Modulus × 160+50 (mm))
7) Unit Height = Casing Height + Base Height (refer to the table of Fan Section Data)