EasyManuals Logo

McQuay WDC User Manual

McQuay WDC
84 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #50 background imageLoading...
Page #50 background image
50 Product Manual PM WSC/WDC
Compressor Motor Data, 50 Hz. (continued)
Nameplate Volts 220 346 380 400 415 440 3300 6000 6600
Voltage Code E Y F G K H J 8 9
Motor
Code
Min/Max Volts 198/242 311/381 342/418 360/440 374/457 396/484 2970/3630 5400/6600 5940/7260
Max kW
191
191
192
191
191
191
Locked Rotor Amps
3281
2311
1688
1771
1849
1640
23
B
Power Factor
.88
.85
.90
.88
.86
.88
Max kW
195
195
195
195
195
195
210
212
211
Locked Rotor Amps
3485
2588
1956
2075
2156
1859
209
108
121
25
B
Power Factor
.88
.85
.89
.87
.85
.87
.89
.90
.87
Max kW
228
228
228
228
228
228
Locked Rotor Amps
3666
2993
2179
2298
2388
1921
31
B
Power Factor
.90
.85
.90
.88
.87
.89
Max kW
271
271
271
Locked Rotor Amps
230
144
135
32
B
Power Factor
.91
.89
.89
Max kW
260
260
260
260
260
260
Locked Rotor Amps
4366
3267
2468
2603
2704
2429
34
B
Power Factor
.90
.88
.90
.89
.88
.89
Max kW
263
263
264
263
263
263
Locked Rotor Amps
4753
2718
2349
2669
2775
2376
35
B
Power Factor
.87
.88
.89
.86
.84
.87
Max kW
293
293
293
293
293
293
328
329
329
Locked Rotor Amps
4664
3771
2793
2946
3061
2429
303
198
180
41
B
Power Factor
.90
.85
.90
.88
.86
.90
.90
.89
.89
Max kW
355
355
355
355
363
Locked Rotor Amps
3901
2979
3143
3267
334
45
C
Power Factor
.85
.88
.86
.84
.91
Max kW
325
325
325
325
325
325
Locked Rotor Amps
5839
3885
3030
3196
3321
2758
47
B
Power Factor .89 .89 .91 .90 .88 .90
Max kW
374
374
374
374
374
374
Locked Rotor Amps
6238
4632
3732
3937
4092
3118
49
B
Power Factor
.89
.86
.89
.86
.84
.89
Max kW
380
380
381
Locked Rotor Amps
339
212
191
50
B
Power Factor
.90
.90
.90
Max kW
395
397
395
Locked Rotor Amps
343
212
224
52
C
Power Factor
.86
.86
.85
Max kW
389
390
389
389
389
Locked Rotor Amps
4655
3752
3958
4113
3547
53
C
Power Factor
.89
.91
.89
.88
.90
Max kW
424
424
424
424
424
424
Locked Rotor Amps
6754
5170
3827
4037
4195
3619
57
B
Power Factor
.90
.87
.90
.89
.88
.89
Max kW
426
Locked Rotor Amps
390
58
B
Power Factor
.91
Max kW
472
474
473
Locked Rotor Amps
445
294
268
59
C
Power Factor
.86
.83
.86
Max kW
467
470
468
468
468
Locked Rotor Amps
5370
3880
4093
4255
3920
62
C
Power Factor
.89
.92
.91
.90
.91
Max kW
482
Locked Rotor Amps
443
65
B
Power Factor
0.91
Max kW
551
551
551
Locked Rotor Amps
480
319
306
71
C
Power Factor
.88
.86
.85
Max kW
545
547
545
545
546
Locked Rotor Amps
6151
4676
4933
5126
4280
73
C
Power Factor
.90
.92
.91
.90
.91
Max kW
653
654
654
Locked Rotor Amps
584
412
333
83
C
Power Factor
.88
.85
.87
Max kW
646
647
646
645
646
Locked Rotor Amps
7143
5743
6059
6297
5541
85
C
Power Factor
.91
.92
.91
.90
.91