Compressor Motor Data, 50 Hz. (continued)
Nameplate Volts 220 346 380 400 415 440 3300 6000 6600
Voltage Code E Y F G K H J 8 9
Motor
Code
Min/Max Volts 198/242 311/381 342/418 360/440 374/457 396/484 2970/3630 5400/6600 5940/7260
Max kW 721
Locked Rotor Amps 439
91
C
Power Factor .84
Max kW 778 780 778 778 780
Locked Rotor Amps 8440 6590 6956 7231 5685
K0
C
Power Factor .90 .91 .91 .89 .91
Max kW 785 784 785
Locked Rotor Amps 738 548 498
N0
C
Power Factor .88 .84 .84
Max kW 842 845 843 844 846 849
Locked Rotor Amps 7795 6930 6658 5975 5565 774
N1
C
Power Factor .88 .88 .88 .89 .89 .89
Max kW 937 935 940 940 938 940
Locked Rotor Amps 8522 8125 6898 6532 6003 867
N2
C
Power Factor .89 .88 .90 .90 .90 .89
Field Wiring
Model WSC/WDC centrifugal chillers require field connected power and interlock wiring to complete their
integration into an operating system.