29
running running
P11.19
Upper limit
of skip
frequency
1
Skip
frequency 1
P11.20~3000.00Hz 0.01Hz 0.00 × ×
P11.20
Lower limit
of skip
frequency
1
Skip
frequency 1
0.00~ P11.19 0.01Hz 0.00 × ×
P11.21
Upper limit
of skip
frequency
2
Skip
frequency 2
P11.22~3000.00Hz 0.01Hz 0.00 × ×
P11.22
Lower limit
of skip
frequency
2
Skip
frequency 2
0.00~ P11.21 0.01Hz 0.00 × ×
P11.23
Upper limit
of skip
frequency
3
Skip
frequency 3
P11.24~3000.00Hz 0.01Hz 0.00 × ×
P11.24
Lower limit
of skip
frequency
3
Skip
frequency 3
0.00~ P11.23 0.01Hz 0.00 × ×
Group P12: Advanced function parameters
P12.02
Carrier
wave
frequency
Carrier wave
frequency
0.7~15.0kHz 0.1 3.0
P12.05
Current
loop
proportion
al gain
Current loop
proportional
gain
1~5000 1 600 ×
P12.06
Current
loop
integral
time
Current loop
integral time
0.5~100.0ms 0.1 8.0 ×
P12.09
Pre-magn
etizing
time
Pre-magneti
zing time
0.0~10.0s 0.1 0.2 × ×
P12.10
Minimum
flux
reference
value
Minimum flux
reference
value
10%~150% 1% 10% ×
P12.11
Flux-weak
ening
adjustmen
t
coefficient
Flux-weakeni
ng
adjustment
coefficient 1
0~10000 1 0 ×

Related product manuals