MI 3250 MicroOhm 10A Safety and operational considerations
7
Warnings related to measurement functions:
Resistance and inductive measurement
Resistance measurement should only be performed on de-energized objects!
Do not touch the test object during the measurement or before it is fully
discharged! Risk of electric shock!
When a resistance measurement has been performed on an inductive object,
automatic discharge may not be done immediately!
High voltage can appear on test terminals when measuring inductive object!
Do not connect test terminals to external voltage higher than 300 V (AC or DC) in
order not to damage the test instrument!
General
Warning will appear on screen and the resistance test will not be performed
if voltages higher than 8 V (AC or DC) are detected between test terminals. There
will be no warning if all terminals are at the same potential.
PASS / FAIL indication is enabled when limit is set. Apply appropriate limit value
for evaluation of measurement results.