14.2.1.3 Hang indoor unit 
1. Please refer to the upper data to locate the 
four positioning screw bolt hole on the ceiling. 
Be sure to mark the areas where ceiling hook 
holes will be drilled. 
2. Install and fit pipes and wires after you have 
finished installing the main body. When 
choosing where to start, determine the 
direction of the pipes to be drawn out. 
Especially in cases where there is a ceiling 
involved, align the refrigerant pipes, drain 
pipes, and indoor and outdoor lines with their 
connection points before mounting the unit. 
3. Install hanging screw bolts. 
• Cut off the roof beam. 
• Strengthen the place that has been cut 
off, and consolidate the roof beam. 
4. After you select an installation location, align 
the refrigerant pipes, drain pipes, as well as 
indoor and outdoor wires with their connection 
points before mounting the unit. 
5. Drill 4 holes 10cm (4”) deep at the ceiling 
hook positions in the internal ceiling. Be sure to 
hold the drill at a 90° angle to the ceiling.     
6. Secure the bolt using the washers and nuts 
provided. 
7. Install the four suspension bolts. 
8. Mount the indoor unit with at least two 
people to lift and secure it. Insert suspension 
bolts into the unit’s hanging holes. Fasten 
them using the washers and nuts provided. 
 
9. Mount the indoor unit onto the hanging 
screw bolts with a block. Position the 
indoor unit flat using a level indicator to 
prevent leaks.             
 
 
Note: Confirm the minimum drain tilt is 1/100 or 
more. 
14.2.1.4 Duct and accessories installation 
1. Install the filter (optional) according to the 
size of the air inlet. 
2. Install the canvas tie-in between the body 
and the duct. 
3. Air inlet and air outlet duct should be apart far 
enough to avoid air passage short-circuit. 
4. Connect the duct according to the following 
diagram. 
 
5.Please refer to the following static pressure to 
install. 
 
Change the fan motor static pressure 
corresponding to external duct static pressure.