14.5 Drainage pipe installation 
Install  the  drainage  pipe  as  shown  below  and 
take  measures  against  condensation. 
Improperly  installation  could  lead  to  leakage 
and eventually wet furniture and belongings. 
 
14.5.1  Installation principle 
  Ensure at least 1/100 slope of the drainage 
pipe 
  Adopt suitable pipe diameter 
  Adopt nearby condensate water discharge 
 
14.5.2  Key  points  of  drainage  water  pipe 
installation 
1.  Considering  the  pipeline  route  and 
elevation 
  Before installing condensate water pipeline, 
determine  its  route  and  elevation  to  avoid 
intersection with other pipelines and ensure 
slope is straight. 
2.  Drainage pipe selection 
  The drainage pipe diameter shall not small 
than the drain hose of indoor unit 
  According  to  the  water  flowrate  and 
drainage pipe slope to choose the suitable 
pipe,  the  water  flowrate  is  decided  by  the 
capacity of indoor unit. 
Relationship  between  water  flowrate  and 
capacity of indoor unit 
According  to  the  above  table  to  calculate  the 
total  water  flowrate  for  the  confluence  pipe 
selection. 
For  horizontal  drainage  pipe  (The  following 
table is for reference) 
Reference 
value  of 
inner 
diameter of 
pipe (mm) 
Allowable 
maximum 
water flowrate 
(l/h) 
Could be used 
for  confluence 
pipe 
Attention: Adopt PVC40 or bigger pipe to be the 
main pipe. 
For  Vertical  drainage  pipe  (The  following 
table is for reference) 
Reference 
value  of 
inner 
diameter  of 
pipe (mm) 
Allowable 
maximum 
water 
flowrate (l/h) 
Could be used 
for  confluence 
pipe 
Attention: Adopt PVC40 or bigger pipe to be the 
main pipe. 
3.  Individual  design  of  drainage  pipe 
system 
  The  drainage  pipe  of  air  conditioner  shall 
be  installed  separately  with  other  sewage 
pipe,  rainwater  pipe  and  drainage  pipe  in 
building. 
  The  drainage  pipe  of  the  indoor  unit  with 
water pump  should  be  apart from the  one 
without water pump. 
4.  Supporter gap of drainage pipe 
  In  general,  the  supporter  gap  of  the 
drainage  pipe  horizontal  pipe  and  vertical 
pipe is respectively 1m~1.5m (3.28~4.92ft) 
and 1.5m~2.0m(4.95~6.56ft).   
  Each  vertical  pipe  shall  be  equipped  with 
not less than two hangers. 
  Overlarge  hanger  gap  for  horizontal  pipe 
shall  create  bending,  thus  leading  to  air 
block.