16.3.8  Condenser  high  temperature  T3 
protection 
---55°C(131°F)<T3<60°C(140°F),  the 
compressor  frequency  will  decrease  to  the 
lower  level  until  to  F1  and  then  runs  at  F1.If 
T3<54°C(129.2°F),  the  compressor  will  keep 
running at the current frequency. 
---T3<52°C(125.6°F),  the  compressor  will  not 
limit  the  frequency  and  resume  to  the  former 
frequency. 
---T3>60°C(140°F)  for  5  seconds,  the 
compressor will stop until T3<52°C(125.6°F). 
16.3.9  Evaporator  low  temperature  T2 
protection 
---T2<0°C(32°F), the compressor will stop  and 
restart when T2≧5°C(41°F). 
---0°C(32°F)≦T2<4°C(39.2°F),  the  compressor 
frequency will be limited and  decreased to the 
lower level 
---4°C(39.2°F)≤T2≤7°C(44.6°F),  the 
compressor will keep the current frequency. 
---T2>7°C(44.6°F),  the  compressor  frequency 
will not be limited. 
 
16.4 Operation Modes and Functions 
16.4.1 Fan mode 
(1) Outdoor fan and compressor stop. 
(2)  Temperature  control  is  disabled  and  no 
temperature setting is displayed. 
(3) Indoor fan can be set to 1%~100%, or low,   
medium, high and auto. 
(4)  The  louver  operates  same  as  in  cooling 
mode. 
(5) Auto fan:   
In fan-only mode, AC operates the same as   
auto fan in cooling mode with the temperature 
set at 24°C. 
16.4.2 Cooling Mode 
16.4.2.1 Outdoor fan running rules 
T4
A DC_FAN_HI_SPD_ADD
B DC_FAN_MID_SPD_ADD
C DC_FAN_MIN_SPD_ADD
D DC_FAN_SLOW_SPD_ADD
E DC_FAN_SSLOW_SPD_ADD
 
16.4.2.2 Indoor fan running rules 
In  cooling  mode,  indoor  fan  runs  all  the  time 
and  the  speed  can  be  selected  as  1%~100%, 
or low, medium, high and auto. 
The indoor fan is controlled as below: 
H+(H+=H+G)
A H(=H)
B
C
M+(M+=M+Z)
D M(M=M)
E
F
L+(L+=L+D)
G L(L=L)
H
I
Auto fan in cooling mode acts as follow: 
For MCD1-24HRFN1-MT0W(GA) 
T1-Tsc
100%
80%
60%
40%
20%
0°C (0°F )
0.5°C (0.9°F )
1.0°C (1.8°F )
1.5°C (2.7°F )
3.5°C (6.3°F )
4.0°C (7.2°F )
1%
-0.5°C (-0.9°F )
Turbo
High
Medium
Low
Silence