15.4.6.7 The setting time is relative time. 
 
16.4.7 Sleep function mode 
16.4.7.1  The  sleep  function  is  available  in 
cooling, heating or auto mode. 
16.4.7.2. Operation process in sleep mode is as 
follow: 
When cooling, the setting temperature rises 1℃
(1.8°F)  (be  lower  than  30℃(86°F))  every  one 
hour,  2  hours  later  the  setting  temperature 
stops  rising  and  the  indoor  fan  is  fixed  at  low 
speed.     
When heating, the setting temperature 
decreases 1℃(1.8°F) (be higher than 17℃
(62.6°F)/ 16℃(60.8°F) 
(MCD1-24HRFN1-MT0W(GA)) every one hour, 
2 hours later the setting temperature stops 
rising and indoor fan is fixed at low speed. 
(Anti-cold wind function has the priority). 
16.4.7.3  Operation  time  in  sleep  mode  is  7 
hours. After 7 hours, the unit does not switch off, 
but for console, the unit switches off. 
16.4.7.4 Timer setting is available. 
 
16.4.8 Auto-Restart function 
The  indoor  unit  is  equipped  with  auto-restart 
function,  which  is  carried  out  through  an 
auto-restart module. In case of a sudden power 
failure,  the  module  memorizes  the  setting 
conditions before the power failure. The unit will 
resume  the  previous  operation  setting  (not 
including  sleep  function)  automatically  after  3 
minutes when power returns. 
 
16.4.9 Follow me 
1)  If the indoor PCB receives the signal which 
results  from pressing  the FOLLOW ME button 
on remote controller or wired remote controller, 
the buzzer will emit a sound and this indicates 
the follow me function is initiated. But when the 
indoor  PCB  receives  signal  which  sent  from 
remote  controller  every  3  minutes,  the  buzzer 
will not respond. When the unit is running with 
follow me function, the PCB will control the unit 
according  to  the  temperature  from  follow  me 
signal, and  the temperature collection function 
of room temperature sensor will be shielded. 
2)  When the follow me function is available, 
the  PCB  will  control  the  unit  according  to  the 
room  temperature  from  the  remote  controller 
and the setting temperature. 
3)  The PCB will take action to the mode 
change  information  from  remote  controller 
signal,  but  it  will  not  affected  by  the  setting 
temperature. 
4)  When the unit is running with follow me 
function, if the PCB doesn’t receive any signal 
from remote controller for 7 minutes or pressing 
FOLLOW  ME  button  again,  the  follow  me 
function will be turned off automatically, and the 
temperature  will  control  the  unit  according  to 
the  room  temperature  detected  from  its  own 
room  temperature  sensor  and  setting 
temperature. 
 
16.4.10 8℃  Heating(optional) 
In heating operation, the preset temperature of 
the  air  conditioner  can  be  as  lower  as  8 ℃
(46.4°F),  which  keeps  the  room  temperature 
steady at 8℃(46.4°F) and prevents household 
things freezing when the  house  is  unoccupied 
for a long time in severe cold weather. 
 
16.4.11 Drain pump control 
Adopt  the  water-level  switch  to  control  the 
action of drain pump. 
Main action under different condition :( every 5 
seconds the system will check  the  water level 
one time) 
1.  When  the  A/C  operates  with  cooling 
(including  auto  cooling),  dehumidifying,  and 
forced  cooling  mode,  the  pump  will  start 
running  immediately and  continuously,  till  stop 
cooling. 
2. Once the water level increase and up to the 
control  point,  LED  will  alarm  and  the  drain 
pump  open  and  continue  checking  the  water 
level.  If  the  water  level  fall  down  and  LED 
disalarmed (drain  pump  delay  close  1  minute) 
and operate with the last mode. Otherwise the 
entire  system  stop  operating  (including  the