---Compressor  discharge  temp.  T5>115 ℃
(239°F)  for  5s,  compressor  stops  and  restarts 
up till T5<90℃(194°F) 
---110<T5<115℃(239°F), decrease the 
frequency to the lower level every 2 minutes. 
---105(221°F)<T5<110℃(230°F),  keep  running 
at the current frequency. 
----T5<105℃(221°F), no limit for frequency. 
16.3.4 Fan speed malfunction 
When  indoor  fan  speed  keeps  too  low  (lower 
than 300RPM) for 50s, the indoor fan will shut 
off and restart 30s later, if protection happened 
3  times  when  fan  motor  restarts  continuously, 
the  unit  will  stop  and  the  LED  will  display  the 
failure. 
When outdoor fan speed keeps too low (lower 
than  100RPM)  or  too  high  (higher  than 
1500RPM)  for  60s,  the  unit  will  stop  and  the 
LED  will  display  the  failure.  Malfunction  is 
cleared 30s later. 
For A6 Duct& HESP Duct: 
If a fault occurs on the air volume regulator or 
the regulator enters protection mode, it sends 
the error message CF and an instruction to 
reduce fan speed to the master. The message 
and the instruction can be inquired with the 
remote controller or the wired controller. (Fault 
and protection information are displayed for 
one minute). After a fault occurs, the master 
unit shows the error code E3 and the fault count 
for one minute. If the fault occurs three times, 
then the fan is unable to resolve the problem 
independently. External shutdown by a remote 
controller, wired controller, or central controller 
must be used to clear the fan fault and fault 
count. The fan runs normally for 5 minutes 
while clearing fault count. 
12:Target speed cannot be met during the 
static pressure calculation process. 
 
16.3.5 Inverter module protection 
The  Inverter  module  has  a  protection  function 
about current, voltage and temperature. If these 
protections  happen,  the  corresponding  code 
will display on indoor unit and the unit will stop 
working. 
16.3.6 Indoor fan delayed open function 
When the unit starts up, the louver will be active 
immediately  and  the  indoor  fan  will  open  7s 
later. 
If the unit runs in heating mode, the indoor fan 
will  be  also  controlled  by  anti-cold  wind 
function. 
16.3.7 Compressor preheating functions 
Preheating permitting condition: 
If  T4<3℃(37.4°F)  and  the  machine  connects 
to power supply newly within 5 seconds or if T4
<3℃(37.4°F) and compressor has stopped for 
over 3 hours, the compressor heating cable will 
work. 
Preheating mode: 
A  weak  current  flow  through  the  coil  of 
compressor  from  the  wiring  terminal  of  the 
compressor,  then  the  compressor  is  heated 
without operation. 
Preheating release condition: 
If  T4≥5 ℃ (41°F)  or  the  compressor  starts 
running, the preheating function will stop.