purge the air (be careful of the liquid 
refrigerant). 
3) Place the charging cylinder onto the 
electronic scale and record the weight. 
4) Turn on the air conditioner in cooling mode. 
5) Open the valves (Low side)on the charge set 
and charge the system with liquid refrigerant. 
6).When  the  electronic  scale  displays  the 
proper  weight  (refer  to  the  gauge  and  the 
pressure of the low side), disconnect the charge 
hose  from  the  3-way  valve’s  service  port 
immediately  and  turn  off  the  air  conditioner 
before disconnecting the hose. 
7). Mount the valve stem caps and the service 
port. 
Use torque wrench to tighten the service port 
cap to a torque of 18N.m. 
Be sure to check for gas leaks. 
 
14.4.5  Re-installation  When  Indoor  Unit 
Requires Repairs 
1.  Collecting  the  Refrigerant  into  the 
Outdoor Unit 
 
Procedure 
1).  Confirm  that  both  the  2-way  and  3-way 
valves are open. 
Remove the  valve stem  caps  and  confirm  that 
the valve stems are open. 
Be sure to use a hexagonal wrench to operate 
the valve stems. 
2). Connect the charge hose with the push pin 
of  handle  lo  to  the  3-way  valves  gas  service 
port. 
3). Purge the air from the charge hose. 
Open the handle Lo valve of the manifold valve 
slightly to purge air from the charge hose for 5 
seconds and then close it quickly. 
4). Close the 2-way valve. 
5). Turn on the air conditioner in cooling mode. 
Turn  it  off  when  the  gauge  indicates 
-0.1MPa(14.5Psi). 
6).Immediately close the 3-way valve   
Do  this  quickly  so  that  the  gauge  displays  a 
value between 0.3 to 0.5 Mpa(43.5 to 72.5Psi). 
Disconnect  the  charge  set,  and  tighten  the 
2-way and 3-way valves’ stem nuts. 
Use a torque wrench to tighten the 3-way valves 
service port cap to a torque of 18N.m. 
Be sure to check for gas leaks. 
 
2. Air Purging by the Refrigerant 
 
Procedure: 
1).  Confirm  that  both  the  2-way  and  3-way 
valves are closed. 
2).  Connect  the  charge  set  and  a  charging 
cylinder to the service port of the 3-way valve 
Leave the valve on the charging cylinder closed. 
3). Purge the air from the charge hose. 
Open  the  valves  on  the  charging  cylinder  and 
the charge  set. Purge  the  air  by loosening the 
flare nut  on  the 2-way valve approximately  45’ 
for 3 seconds and then closing it  for  1 minute. 
Repeat 3 times. 
After  purging  the  air,  use  a  torque  wrench  to 
tighten the flare nut on the 2-way valve. 
4). Check for gas leaks 
Check the flare connections for gas leakage. 
5). Discharge the refrigerant. 
Close  the  valve  on  the  charging  cylinder  and 
discharge the refrigerant by loosening the flare