17.4.6 Refrigerant Leakage Detection diagnosis and solution (EC) 
Define the evaporator coil temperature T2 of the compressor 
starts running as Tcool.   
If the following occurs 3 times, the display shows "EC" and the 
unit switches off: 
In the first 8 minutes after the compressor starts up, if T2  <
Tcool-2℃  is not maintained for 4 seconds and compressor 
running frequency is not higher than 50Hz for 3 minutes 
●  Faulty T2 sensor 
●  Faulty indoor PCB 
●  System problems, such as leakage or blockages 
Trouble shooting: 
Is there cool air blowing 
out from indoor air outlet?
Yes
Yes
Check the T2 
sensor. Is it 
securely attached?
No
Check system for leakages. 
Are any leakages present?
No
Power off, then restart the 
unit 2 minutes later. Does a 
problem still remain?
Replace the indoor 
PCB
Yes
Repair the leakage and 
recharge the refrigerant
Yes
Check System for blockages 
and clear blockages if present