J1 displayed
J1 displayed
High temperature protection of 
condenser 
High temperature protection of 
condenser 
Is the condenser 
temperature is Higher  than 
65°C?
Is the condenser 
temperature is Higher  than 
65°C?
Yes
Is the resistance of 
condenser temp. sensor 
normal according to 
Appendix 1
Is the resistance of 
condenser temp. sensor 
normal according to 
Appendix 1
Replace the temperature sensor
Replace the temperature sensor
No
No
Is the outdoor ambient 
temperature higher than 
50℃?
Is the outdoor ambient 
temperature higher than 
50℃?
No
Stop the unit 
Stop the unit Yes
Is the outdoor unit ventilation 
functioning properly?
Is the outdoor unit ventilation 
functioning properly?
Yes
Ensure that the outdoor unit 
ventilate is functioning properly
Ensure that the outdoor unit 
ventilate is functioning properly
Is the heat exchanger dirty?
Is the heat exchanger dirty?
No
Clean the heat exchanger
Clean the heat exchangerYes
Check whether the refrigerant 
system is functioning normally
Check whether the refrigerant 
system is functioning normally
 Replace outdoor main 
board. Has the problem 
been resolved?
 Replace outdoor main 
board. Has the problem 
been resolved?
No
If the  level of refrigerant is not 
sufficient, does the system work after 
refrigerant is added?
If the  level of refrigerant is not 
sufficient, does the system work after 
refrigerant is added?
No
Is  the outdoor fan running 
properly?
Is  the outdoor fan running 
properly?
Refer to the solution to the 
malfunction of fan speed being out of 
control . Find the cause and resolve the 
problem.
Refer to the solution to the 
malfunction of fan speed being out of 
control . Find the cause and resolve the 
problem.
No
Yes
No
Correct the connection
Correct the connectionNo
Yes
Is the connection between 
temperature sensor and 
PCB in working order?
Is the connection between 
temperature sensor and 
PCB in working order?
Yes