After flared the pipe, the opening part must 
be  seal  by  end  cover  or  adhesive  tape  to 
avoid duct or exogenous impurity come into 
the pipe. 
7.  Drill  holes  if  the  pipes  need  to  pass  the 
wall. 
8.  According  to  the  field  condition  to  bend 
the  pipes  so  that  it  can  pass  the  wall 
smoothly. 
9.  Bind and wrap the wire together with the 
insulated pipe if necessary. 
10.  Set the wall conduit 
11.  Set the supporter for the pipe. 
12.  Locate the pipe and fix it by supporter 
  For horizontal refrigerant pipe, the distance 
between supporters should  not  be  exceed 
1m. 
  For  vertical  refrigerant  pipe,  the  distance 
between supporters should  not  be  exceed 
1.5m. 
13.  Connect  the  pipe  to  indoor  unit  and 
outdoor unit by using two spanners. 
  Be  sure  to  use  two  spanners  and  proper 
torque  to  fasten  the  nut,  too  large  torque 
will damage the flare, and too small torque 
may  cause  leakage.  Refer  the  following 
table for different pipe connection. 
 
 
14.4.3  First-Time Installation 
Air and moisture in the refrigerant system 
cause the following problems:   
●  Increases in system pressure 
●  Increases in operating current 
●  Decreases in cooling and heating efficiency 
●  Blocks  in  capillary  tubing  caused  by 
moisture in the refrigerant circuit freezing 
●  Corrosion of parts in the refrigerant system 
caused by water 
The indoor units and the pipes between 
indoor and outdoor units must be tested for 
leakages and evacuated to remove gas and 
moisture from the system. 
 
Gas leak check with soap water: 
Apply soap water or a liquid neutral 
detergent on the connections with a soft brush 
to check for leakage in the pipe connecting 
points. If bubbles emerge, the pipes are 
leaking. 
1. Air Purging Using the Vacuum Pump 
 
1)  Completely  tighten  the  flare  nuts  on  the 
indoor and outdoor units. Confirm that both 
the2-way  and  3-way  valves  are  set  to  the 
closed position. 
2)  Connect the charge hose with the push pin 
of  the  Handle  Lo  to  the  3-way  valve  gas 
service port. 
3)  Connect the charge hose of the Handle Hi 
to the vacuum pump.