For other models, 
a
b
c
d
6.0°C(10.8°F)
T1-Td
e
H
(H-L)*0.75+L
(H-L)*0.5+L
(H-L)*0.25+L
L
5.0°C(9.0°F)
4.0°C(7.2°F)
2.5°C(4.5°F)
1.0°C(1.8°F)
 
16.4.3 Heating Mode 
16.4.3.1 Outdoor fan running rules 
T4
E DC_FAN_SSLOW_SPD_ADD
D DC_FAN_SLOW_SPD_ADD
C DC_FAN_MIN_SPD_ADD
B DC_FAN_MID_SPD_ADD
A DC_FAN_HI_SPD_ADD
 
16.4.3.2 Indoor fan running rules 
When the compressor is on, the indoor fan can 
be set to high/med/low/auto. And the anti-cold 
wind function has the priority. 
The indoor fan is controlled as below: 
 
Auto fan action in heating mode: 
For MCD1-24HRFN1-MT0W(GA), 
T1-Tsc
100%
20%
40%
60%
80%
-3.0°C (-5.4°F )
-1.5°C (-2.7°F )
0°C (0°F )
0.5°C (0.9°F )
1.0°C (1.8°F )
Silence
Low
Medium
High
Turbo
 
For other models, 
0.0°C(0°F)
T1-Td+1.5°C(34.7°F)
L
(H+-L)*0.2+L
(H+-L)*0.4+L
(H+-L)*0.6+L
H+
(H+-L)*0.8+L
-1°C(-1.8°F)
-2°C(-3.6°F)
-3°C(-5.4°F)
-4°C(-7.2°F)
-5°C(-9°F)
-6°C(-10.8°F)
-6.5°C(-11.7°F)
 
16.4.3.3 Defrosting mode 
For MOBA30-09HFN1-MT0W, 
MOB01-09HFN1-MW0W(22022016011384), 
MOB01-12HFN1-MV0W(22022016011383), 
MOB30-12HFN1-MT0W, 
MOCA01-18HFN1-MT0W(22022016011382) , 
MOD01-23HFN1-MT0W(22022016011381), 
MOE30U-36HFN1-M-[X], 
MOD30U-36HFN1-MP0, 
MOE30U-48HFN1-M-[X], 
MOX230-09HFN1-MW5W, 
MOX230-12HFN1-MV5W, 
MOX330-09HFN1-MY5W, 
MOX330-12HFN1-MW5W, 
MOX430-17HFN1-MT0W, 
MOD30-24HFN1-MU0W, 
MOD33-24HFN1-MT0W 
If any one of the following items is satisfied, AC 
will enter the defrosting mode. 
After  the  compressor  starts  up  and  keeps 
running,  mark  the  minimum  value  of  T3  from 
the 10th minutes to 15th minutes as T30. 
1)If the compressor cumulate running time is up 
to  29  minutes  and  T3<  TCDI1,  T3 +
T30SUBT3ONE<T30, T4>-22℃(-7.6°F). 
2)If the compressor cumulate running time is up 
to  35  minutes  and  T3<  TCDI2,  T3 +
T30SUBT3TWO<T30, T4>-22℃(-7.6°F). 
3)If the compressor cumulate running time is up 
to  29  minutes  and  T3<  -24℃(-11.2°F),  T4>
-22℃(-7.6°F) for 3 minutes.