4)  If  the  compressor  cumulate  running time  is 
up  to  30  minutes  and  T4-T3  >  (0.5T4+ 
KDELTT_ADD), T3 < TCDIN5_ADD, T4>-22℃
(-7.6°F). 
5)  If  the  compressor  cumulate  running  time  is 
up to TIMING_DEFROST_TIME and T4≦-22℃
(-7.6°F). 
6)  T3  is  lower  than  3°C(37.4°F)  and  the 
compressor cumulate running time is up to 120 
minutes, at this time, if T3≦TCDI1+4℃(39.2°F) 
for 3 minutes. 
Condition of ending defrosting: 
If any one of the following items is satisfied, the 
defrosting will finish and the machine will turn to 
normal heating mode. 
----T3 rises to be higher than TCDE1. 
----T3  keeps  to  be  higher  than  TCDE2  for  80 
seconds. 
----The  machine  has  run  for  15  minutes  in 
defrosting mode. 
If the  fifth  item is satisfied  and any one  of  the 
following  items  is  satisfied,  the  defrosting  will 
finish  and  the  machine  will  turn  to  normal 
heating mode. 
----T3 rises to be higher than 10℃(50°F). 
---The  machine  has  run  for  10  minutes  in 
defrosting mode. 
If the sixth item is satisfied and any one of the 
following  items  is  satisfied,  the  defrosting  will 
finish  and  the  machine  will  turn  to  normal 
heating mode. 
----T3  rises  to  be  higher  than  TCDE1+4 ℃
(39.2°F). 
----T3  keeps  to  be  higher  than  TCDE2+4 ℃
(39.2°F) for 80 seconds. 
----The  machine  has  run  for  15  minutes  in 
defrosting mode. 
 
Defrosting action: 
compressor
4-way valve
Outdoor fan
膨胀阀
OFF
ON
ON
ON
OFF
OFF
ON
ON
f2
No longer than 15 min
10s
PMV_NOR_HEAT_DEFORST_
EE
480步 480步
正常化霜示意图
阶段1 阶段2 阶段3
阶段4
阶段5
DEFORSTFRE_ADD
 
For other outdoor units, 
If any one of the following items is satisfied, AC 
will enter the defrosting mode. 
After  the  compressor  starts  up  and  keeps 
running,  mark  the  minimum  value  of  T3  from 
the 10th minutes to 15th minutes as T30. 
1)If the compressor cumulate running time is up 
to  29  minutes  and  T3<  TCDI1,  T3 +
T30SUBT3ONE≦T30. 
2)If the compressor cumulate running time is up 
to  35  minutes  and  T3<  TCDI2,  T3 +
T30SUBT3TWO≦T30. 
3)If the compressor cumulate running time is up 
to 40 minutes and T3< TCDI3 for 3 minutes. 
4)  If  the  compressor  cumulate  running time  is 
up  to  30  minutes  and  T4-T3  >  (0.5T4+ 
KDELTT_ADD) and T3 < TCDIN5_ADD. 
 
Condition of ending defrosting: 
If any one of the following items is satisfied, the 
defrosting will finish and the machine will turn to 
normal heating mode. 
----T3 rises to be higher than TCDE1. 
----T3  keeps  to  be  higher  than  TCDE2  for  80 
seconds. 
----The  machine  has  run  for  10  minutes  in 
defrosting mode. 
Defrosting action: