Part 3 - Installation and Field Settings 
Figure 3-7.43: Preheating for floor screens 
 
7.15.3  FLOOR DRYING UP 
MENU > FOR SERVICEMAN > SPECIAL FUNCTION > FLOOR 
DRYING UP 
 
For newly-installed under-floor  heating  systems, floor drying 
up mode can be used to remove moisture from the floor slab 
and subfloor to prevent warping or rupture of the floor during 
floor  heating  operation.  There  are  three  phases  to  the floor 
drying up operation: 
  Phase 1: gradual temperature increase from a starting point of 25°C to the peak temperature 
  Phase 2: maintain peak temperature 
  Phase 3: gradual temperature decrease from the peak temperature to 45°C 
 
t_DRYUP sets the duration of Phase 1. 
 
t_HIGHPEAK sets the duration of Phase 2. 
 
t_DRYDOWN is the duration of Phase 3. 
 
T_DRYPEAK sets the heat pump’s leaving water set temperature for Phase 2. 
 
START TIME sets the floor drying up operation start time. 
 
START DATE sets the floor drying up operation start date. 
 
The heat pump’s leaving water set temperature during the floor drying up operation is illustrated in Figure 3-7.40. 
 
During  the  floor  drying  up operation  all  buttons  except  OK  are inactivated.  To exit 
the floor drying up operation, press OK and then select YES when prompted. 
 
Note: In the event of a heat pump malfunction, floor drying up mode will continue if 
a backup electric heater and/or additional heating source is available and configured 
to support space heating mode.   
   
12.1 PREHEATING FOR FLOOR
Preheat for floor is
running for 25 minutes.
Water flow temperature is 20°C.
OK CONFIRM
12.1 PREHEATING FOR FLOOR
Do you want to turn off the preheating
for floor function?
OK CONFIRM
NO YES
Figure 3-7.44: FLOOR DRYING UP menu   
Figure 3-7.45: FLOOR DRYING UP settings 
Figure 3-7.46: FLOOR DRYING UP screen 
12.2 FLOOR DRYING UP
8 days
5 days
5 days
45°C
15:00
ADJUST
t_DRYUP
t_HIGHPEAK
t_DRYDOWN
T_DRYPEAK
START TIME
12.2 FLOOR DRYING UP
01-01-2019
ADJUST
START DAY
ENTER                     EXIT
12.2 FLOOR DRYING UP
01-01-2019
ADJUST
START DAY
ENTER                     EXIT