Part 3 - Installation and Field Settings 
7.14.6  HEAT MODE RUNNING operation 
The  HEAT  MODE  RUNNING  operation  is  used  to  check  the  operation  of  the 
system in space heating mode. 
 
During the HEAT  MODE RUNNING  operation  the  M thermal Split unit leaving 
water set temperature is 35°C. The current actual leaving water temperature is 
displayed  on  the  user  interface.  When  the  HEAT  MODE  RUNNING  operation 
starts, the heat pump first runs for 10 mins.   
 
After 10 mins: 
  On  systems where  an auxiliary  heat  source  (AHS)  is  installed,  the  AHS  starts  and runs  for 10 mins (whilst the heat 
pump  continues  running),  after  which  the  AHS  stops  and  the  heat  pump  continues  to  operate  until  the  water 
temperature rises to the set temperature or the heat mode running operation is exited by pressing OK. 
  On systems where a backup electric heater is being used, the backup heater turn on (on models where the backup 
heater has a simple on/off control function). 3 mins later the backup electric heater will turn off. The heat pump will 
then operate until the water temperature rises to the set temperature or the next command is received. 
  On systems with no auxiliary heat source (AHS), the heat pump will then operate until the water temperature rises to 
the set temperature or the next command is received. 
 
If any error code is displayed during the cool mode running operation, the cause should be investigated. Refer to Part 3, 8.2 
“Error Code table”. 
 
7.14.7  DHW MODE RUNNING operation 
The DHW MODE RUNNING operation is used to check the operation of the system in DHW mode. 
 
During the DHW MODE RUNNING operation, the DHW set temperature is 55°C. On systems where a tank boost heater is 
installed, the tank boost heater will turn on once the heat pump has run for 10 mins. The tank boost heater will turn off 3 
mins later and the heat pump will operate until the water temperature rises to the set temperature or the next command 
is received. 
 
Figure 3-7.39: DHW MODE RUNNING display 
   
11 TEST RUN
Test run is on.
DHW mode is on.
Water flow temper. is 45°C
Water tank temper. is 30°C
OK CONFIRM
Figure 3-7.38: HEAT MODE RUNNING display 
11 TEST RUN
Test run is on.
Heat mode is on.
Leaving water temperature is
15°C.
OK CONFIRM